Product
产品信息
产品信息

| Product summary | Detects overcurrent / locked rotor current and protects a motor from burnout |
|---|---|
| Product purpose | Prevent burnout of general-purpose three-phase motors |
| Intended use | Submerged pump |
| Operating type | Bimetal type (Convert a current applied to the product into heat in the internal heater, which then operates the bimetal and interrupts the circuit) |
| Compatible standard | UL (with some exceptions) |
| Case material | Phenolic resin |
|---|---|
| Operating temperature range | Temperature near motor: 20°C to 100°C |
| Connection terminal type | Solder incurved terminal |
| Product mounting method | Fixed in place with M4 screws or by other means |
| Rated voltage | AC 250/500V |
|---|---|
| Rated capacity | Up to 15 kW |
| Contact withstand current | 300/200A |
| Contact withstand count | 1,000 times or more |
| Withstand voltage | 1500 V for 1 minute |
| Insulation resistance | 50 MΩ or higher with a 500-VDC megohmmeter |