| Product summary | Detects overcurrent / locked rotor current and protects a motor from burnout | 
|---|---|
| Product purpose | Prevent burnout of general-purpose three-phase motors | 
| Intended use | Submerged pump | 
| Operating type | Bimetal type (Convert a current applied to the product into heat in the internal heater, which then operates the bimetal and interrupts the circuit) | 
| Compatible standard | UL | 
| Case material | Phenolic resin | 
|---|---|
| Operating temperature range | Temperature near motor: 20°C to 100°C | 
| Connection terminal type | Solder incurved terminal | 
| Product mounting method | Fixed in place with M4 screws or by other means | 
| Rated voltage | AC 250/500V | 
|---|---|
| Rated capacity | Up to 1.0 kW | 
| Contact withstand current | 30/20A | 
| Contact withstand count | 5,000 times or more | 
| Withstand voltage | 1500 V for 1 minute | 
| Insulation resistance | 50 MΩ or higher with a 500-VDC megohmmeter | 

| Product summary | Detects overcurrent / locked rotor current and protects a motor from burnout | 
|---|---|
| Product purpose | Prevent burnout of general-purpose three-phase motors | 
| Intended use | Submerged pump | 
| Operating type | Bimetal type (Convert a current applied to the product into heat in the internal heater, which then operates the bimetal and interrupts the circuit) | 
| Compatible standard | UL (with some exceptions) | 
| Case material | Phenolic resin | 
|---|---|
| Operating temperature range | Temperature near motor: 20°C to 100°C | 
| Connection terminal type | Solder incurved terminal | 
| Product mounting method | Fixed in place with M4 screws or by other means | 
| Rated voltage | AC 250/500V | 
|---|---|
| Rated capacity | Up to 2.2 kW | 
| Contact withstand current | 80/50A | 
| Contact withstand count | 3,000 times or more | 
| Withstand voltage | 1500 V for 1 minute | 
| Insulation resistance | 50 MΩ or higher with a 500-VDC megohmmeter | 

| Product summary | Detects overcurrent / locked rotor current and protects a motor from burnout | 
|---|---|
| Product purpose | Prevent burnout of general-purpose three-phase motors | 
| Intended use | Submerged pump | 
| Operating type | Bimetal type (Convert a current applied to the product into heat in the internal heater, which then operates the bimetal and interrupts the circuit) | 
| Compatible standard | UL (with some exceptions) | 
| Case material | Phenolic resin | 
|---|---|
| Operating temperature range | Temperature near motor: 20°C to 100°C | 
| Connection terminal type | Solder incurved terminal | 
| Product mounting method | Fixed in place with M4 screws or by other means | 
| Rated voltage | AC 250/500V | 
|---|---|
| Rated capacity | Up to 7.5 kW | 
| Contact withstand current | 200/150A | 
| Contact withstand count | 2,000 times or more | 
| Withstand voltage | 1500 V for 1 minute | 
| Insulation resistance | 50 MΩ or higher with a 500-VDC megohmmeter | 

| Product summary | Detects overcurrent / locked rotor current and protects a motor from burnout | 
|---|---|
| Product purpose | Prevent burnout of general-purpose three-phase motors | 
| Intended use | Submerged pump | 
| Operating type | Bimetal type (Convert a current applied to the product into heat in the internal heater, which then operates the bimetal and interrupts the circuit) | 
| Compatible standard | UL (with some exceptions) | 
| Case material | Phenolic resin | 
|---|---|
| Operating temperature range | Temperature near motor: 20°C to 100°C | 
| Connection terminal type | Solder incurved terminal | 
| Product mounting method | Fixed in place with M4 screws or by other means | 
| Rated voltage | AC 250/500V | 
|---|---|
| Rated capacity | Up to 15 kW | 
| Contact withstand current | 300/200A | 
| Contact withstand count | 1,000 times or more | 
| Withstand voltage | 1500 V for 1 minute | 
| Insulation resistance | 50 MΩ or higher with a 500-VDC megohmmeter | 

| Product summary | Detects overcurrent / locked rotor current and protects a motor from burnout | 
|---|---|
| Product purpose | Prevent burnout of general-purpose three-phase motors | 
| Intended use | Submerged pump | 
| Operating type | Bimetal type (Convert a current applied to the product into heat in the internal heater, which then operates the bimetal and interrupts the circuit) | 
| Compatible standard | UL (with some exceptions) | 
| Case material | Phenolic resin | 
|---|---|
| Operating temperature range | Temperature near motor: 20°C to 100°C | 
| Connection terminal type | Thread-fastening terminal | 
| Product mounting method | Fixed in place with M5 screws or by other means | 
| Rated voltage | AC 250/500V | 
|---|---|
| Rated capacity | Up to 37 kW | 
| Contact withstand current | 600/400A | 
| Contact withstand count | 1,000 times or more | 
| Withstand voltage | 1500 V for 1 minute | 
| Insulation resistance | 50 MΩ or higher with a 500-VDC megohmmeter |